Skip to content
Brent$104.61Gas TTF$906USD446.56 ₸
MunaiHub

Voltage dip at motor starting

Estimate of the voltage dip on the substation busbars during direct-on-line starting of an induction motor, and of its reduced starting torque — to check whether a large pump or compressor can be started from a given transformer.

Formula
S_st = √3 · U · K_i · I_nS_k = S_t / u_kΔU = S_st / (S_st + S_k)M_st / M_st,n = (1 − ΔU)²

Only the transformer impedance is included: the supply network and the cable increase the dip, while adding impedance magnitudes without their angles gives a small margin. The substation load before starting is not included. The starting torque falls with the square of the voltage: pumps started against a closed valve usually have a margin, pumping units and reciprocating compressors must be checked. If the dip is large, use a soft starter or a variable frequency drive.

Source: Estimate from the transformer short-circuit power (impedance addition method)

Inputs

You can change a field's unit: the value is converted to the formula's units automatically.

U

Line-to-line voltage on the motor side: 380 V, 6 or 10 kV.

I_n
Calculate
K_i

From the motor catalogue: usually 5–8 direct-on-line.

S_t
Calculate
u_k

From the nameplate; oil-immersed 6–10/0.4 kV transformers: up to 400 kVA about 4.5 %, 630–1 000 kVA 5.5 %, 1 600–2 500 kVA 6 %.

Unit converter for this formulaVoltage · Current · Apparent power · Fraction and percent
  • V1
  • kV0.001
All units
Result
ΔUVoltage dip at starting
Fill in all fields
  • U_stBusbar voltage during starting
  • M_stStarting torque, % of the rated value
  • S_stMotor starting kVA

More in Motors and transformers

Results are engineering estimates from standard formulas; for design decisions check them against the codes, project documents and specialists' calculations. The formulas carried over from the original set are unchanged, and their errors are described in the notes.